Tubes used for insulation and anti-tracking purposes in termination kits
Property | Test Method | Standard Value |
---|---|---|
Tensile Strength(MPa) | ASTM-D-638 | ≥8MPa |
Elongation at Break | ASTM-D-638 | ≥300% |
Tensile Strength Variation After Heat Aging(130℃x168h) | ASTM-D-5510 | ≤±30% |
Elongation at Break Variation After Heat Aging(130℃x168h) | ASTM-D-5510 | ≤±30% |
Volume resistivity | IEC 60243 | ≥1×1014Ω.cm |
Dieletric strength | IEC 60243 | ≥20kV/mm |
Tracking Resistance | IEC 60587 | 1A 3.5 |
Dielectric Constant | IEC 60250 | ≤5 |
Heat Shock | 160℃,4h | No Crack |
Water Absorption (23±2)℃ 24h | ISO 62 | ≤0.1% |
Hardness(Shore A) | ISO 868 | ≥80 |
Brittle Temperature | ISO 974 | -40℃ |
As Supplied/mm | After Recovered/mm | Standard Cut Length /mm | Standard Continous Length(m/roll) | Inner Diameter min | Wall Thickness (±0.3) | Inner Diameter max | Wall Thickness (±0.3) |
---|---|---|---|---|---|
30 | 1 | 12 | 2.2 | 600-1200 | 25 |
35 | 1 | 14 | 2.3 | 600-1200 | 25 |
40 | 1 | 17 | 2.3 | 600-1200 | 25 |
50 | 1 | 22 | 2.5 | 600-1200 | 25 |
35 | 1.2 | 13 | 3 | 600-1200 | 25 |
40 | 1.2 | 15 | 3 | 600-1200 | 25 |
50 | 1.1 | 19 | 3 | 600-1200 | 25 |
55 | 1.4 | 24 | 3.2 | 600-1200 | 25 |
60 | 1.4 | 26 | 3.2 | 600-1200 | 15 |
70 | 1.4 | 29 | 3.2 | 600-1200 | 15 |
75 | 1.5 | 35 | 3.2 | 600-1200 | 15 |
80 | 1.4 | 36 | 3.2 | 600-1200 | 15 |
90 | 1.6 | 45 | 3.5 | 600-1200 | 15 |
100 | 1.5 | 45 | 3.5 | 600-1200 | 15 |
Features –
Material –
Manufactured using crosslinked radiation crosslinked polyolefins
Application –
Used in medium voltage heat shrink termination and jointing kits for protection against
accidental flashover