The Lightning Arrester Coverage Area Calculation (or Air Terminal) is defined as the area within which the arrester effectively protects a structure from lightning strikes. This area depends on the spacing between air terminals. In this blog, we will explain how to calculate the Lightning Arrester’s Coverage Area for both Conventional Lightning Arresters and Early Streamer Emission (ESE) Lightning Arresters.
Let’s start by understanding what is a Lightning Arrester. A Lightning Arrester is the primary component of the Lightning Protection System. It directs lightning charges to the ground via a low-resistance path, preventing damage to electrical systems. There are two types of Lightning Arresters in use: Conventional Lightning Arresters or Franklin Rods and second one is the Early Streamer Emission (ESE) Lightning Arresters.
The Lightning Arrester Coverage Area Calculation is based on the required structure or area to be protected, can be calculated using the method described in IEC 62305-3.
IEC 62305-3 outlines three methods for designing the external lightning protection system. These methods calculate the coverage area:
In this method, an imaginary sphere rolls over the structure. You can use suitable software to perform this exercise. The coverage area is the portion below the two edges of the imaginary sphere that contact the structure. After rolling the sphere over the entire structure, you can determine the effective coverage area.
Watch our video to understand this method in detail
The radius of the rolling sphere is determined based on the level of protection. According to the standard, the radius for each level is as follows:
In this method, you must consider the length and position of the air termination rod. This configuration ensures that the conical volume formed by the vertical rod and the angle defined in the standard protects the structure. The coverage area will include the area under the conical volume within the defined angle.
This method uses a conductor to form a mesh over the entire structure. The mesh’s size depends on the protection level, as defined in the standard. The coverage area includes the area of the structure beneath the mesh formed by the conductor.
The formula for calculating the distance between two Conventional Lightning Arresters(d) According to Rolling Sphere Method
d = 2 * √(2rh – h²)
Where:
This formula calculates the maximum distance that can exist between two air terminals to ensure effective lightning protection. It takes into account the radius of the rolling sphere (which varies depending on the level of protection required) and the height of the air terminal above the horizontal plane.
Here’s an example for better understanding. Let’s say for a Level IV protection system, the given values are:
Substituting these values into the formula, we get:
d = 2 * √(2600.5 – (0.5)²) = 15.46 m
This means that for a Level IV protection system, the maximum distance between two air terminals should not exceed 15.46 meters to ensure effective lightning protection.
ESE Lightning Protection Systems offer a relatively new approach to lightning hazards. According to the standards (NFC 17-102, UNE 21186), they provide the most effective protection.
The coverage area for the lightning protection system can be calculated according to NFC 17 102-2011. The coverage area falls under the umbrella-shaped semicircle, formed by the protection radius. The height of the ESE arrester, installed relative to the surface and above the structure, is a key factor in this calculation.
The ESE must be positioned to protect the structure and the area around it. Ideally, you should install it on the highest point of the structure. This positioning maximizes the protection provided by the ESE. An ESE arrester’s efficiency (ΔT) is proved in the evaluation test as per NFC 17 102-2011. The maximum ΔT value is 60 µs.
The protection radius of an ESE is related to its height (h) relative to the surface to be protected, to its efficiency and to the selected protection level, it is calculated with the below formula:
Where,
Nowadays, the world is spending billions of dollars on building new solar plants. Some of…
Eye hooks are critical fittings used with dead-end and suspension clamps to support Aerial Bundled…
In this blog, we will discuss some common mistakes most people make while installing earthing.…
Suspension clamps are used to suspend and grip neutral messenger cables in Low Voltage Aerial…
The International Electrotechnical Commission (IEC) prepares and publishes International Standards, such as IEC 62305, for…
In this blog, we will talk about the tools required for installing MV Covered Conductor…