Technical Data 1
Property Test method Standard
Heat Shock 160℃,4h No Crack
Tensile Strength ASTM-D-638 ≥8MPa
Elongation at Break ASTM-D-638 ≥300%
Tensile Strength Variation After Heat Aging(130℃x168h) ASTM-D-5510 ≤±20%
Elongation at Break Variation After Heat Aging(130℃x168h) ASTM-D-5510 ≤±20%
Flammability(Oxygen Index) IEC 4589 ≥30%
Technical Data 2
 
Item Test method Standard value 10 kV Standard value 35 kV
Volume Resistivity IEC 60093 ≥1×1014Ω·cm
Dielectric Strength IEC 60243 ≥25kV/mm
Power Frequency Voltage  DL/T 1059 42kV 95kV
Withstanding Impulse Voltage DL/T 1059 75kV 185kV
10kV WMPG
 
As Supplied/mm After Recovered/mm  Standard Length /mm(±5) Application /mm
ID (Min) Wall Thickness (±20%) ID (Max) Wall Thickness (±20%) Width of Rectangular Busbar Diameter of Circular Busbar
20 1 10 2.4 1000 20 15
25 1 12 2.4 1000 25 15
30 1.1 14 2.4 1000 30 20
40 1 17 2.4 1000 40 30
50 1.1 22 2.7 1000 50 35
65 1.1 28 2.7 1000 64 45
75 1.1 32 2.7 1000 75 50
85 1.1 37 2.7 1000 85 65
100 1.1 43 2.7 1000 100 75
120 1.1 53 2.7 1000 120 85
140 1.1 65 2.7 1000 150 100
180 1.1 75 2.7 1000 180 125
200 1.1 88 2.7 1000 200 150
220 1 88 2.7 1000 / /
250 1.5 107 3.6 1000 / /
290 1.3 107 3.8 1000 / /
325 1.1 107 3.8 1000 / /
350 1.2 159 2.7 1000 / /
400 1.2 185 2.7 1000 / /
500 1.2 210 3 1000 / /
35kV WMPG
 
As Supplied/mm After Recovered/mm  Standard Length /mm(±5) Application /mm
ID (Min) Wall Thickness (±20%) ID (Max) Wall Thickness (±20%) Width of Rectangular Busbar Diameter of Circular Busbar
20 2.4 10 4.5 1000 20 15
25 2 10 4.5 1000 20 15
30 2.4 14 4.5 1000 30 20
40 2.2 17 4.5 1000 40 30
50 2.2 21 4.8 1000 50 35
65 2.2 27 5 1000 64 45
75 2.2 31 5 1000 75 50
85 2 32 5 1000 85 55
100 2 38 5 1000 100 75
120 2.1 50 5 1000 120 85
140 2.1 59 5 1000 150 105
180 2.3 71 5.5 1000 180 125
200 2.2 88 5 1000 200 140
220 2 88 5 1000 / /
Features

Features

Shrink Temperature starts at 70℃ and fully recovered at 130℃

Application

Used to offer insulation protection for busbar in switchgear and substation. Protects against short circuit and electrical leakage caused by small animals.

Material –

Cross-linked Polyolefin