Illustration showing how to use lightning arrester on building

How to install lightning arrester on building?

Lightning arrester rods, surge arresters, or lightning conductors are metal rods installed on a building for lightning protection. They protect structure or substations from the travelling waves of lightning and divert the abnormally high voltage to the ground.

The arresters are made from copper and brass alloy that are the best conductors of electricity and have very high ground coverage (up to 60 meters.) A lightning arrester generally has three parts: the first is a rod of about 3ft in length and 12 to 16 mm in diameter. The second part is a spiked ball/receiver (the number of spikes may vary depending on availability) making it easy to be attached to one end of the rod. The third part is a copper-coated brass plate that is screwed to the ground and on which the rod is easily fitted.

 

Install Lightning Arresters on Building for Ensuring Safety!

The primary reason to install lightning arrester on building is to protect them from the hazardous impacts of lightning. Lightning arresters or rods intercept this voltage and provide a safe path for the lightning current into the ground. While it does not decrease the likelihood of a building being struck by lightning, it gives a direct trail to the ground preventing the structure from being damaged from fire, explosion, and electrical surges resulting from lightning strikes.

During a lightning strike, it preferentially strikes the arrester instead of passing through the structure where it could start a fire or cause electrocution. The arrester conducts the current to the ground through a wire. Lightning rods are also called finials, air terminals, or strike termination devices.

The arresters are designed and developed following UL (Underwriter Laboratories) standards. While choosing lightning arresters, these manufacturing standards must be verified. 

The lightning arresters can be: 

1 - A simple rod or with a triggering system. It is a metallic capture tip placed at the top of the building. It is earthed by one or more conductors (often copper strips) 

2 - With taut wires stretched above the structure to be protected. They are used to protect particular structures such as rocket launching areas, military applications, and the protection of high-voltage overhead lines. 

3 - A lightning conductor with mesh cage (Faraday cage) in this type, numerous down conductors/tapes are symmetrically placed all around the building.  

 

This type of lightning protection system is used for highly exposed buildings, housing sensitive installations such as computer rooms.

 

Installation

The arresters installations are as per the international standards as followed in a region or country.
Lightning arresters are part of the external lightning protection installation and are installed on the roof of the building to intercept any lightning before it strikes the structure. IEC 62305 PART 1 to 4 defines guidelines for the system of lightning protection conductors and lightning rods.

As a single component of lightning protection, lightning arresters require a connection to the earth to ensure protective function. They come in many different forms, including hollow, solid, pointed, rounded, flat strips, or bristle brush-like. These rods have one main common attribute, they are all made of conductive materials such as copper and aluminium. Copper and its alloys are the most common materials used in lightning protection.

 

Prerequisites

Choosing the right arrester 

  • UL listed (or equivalent) in the country of installation for lightning surge protection 
  • Must be capable of limiting an incoming surge to 10 kV 

Choosing the right vendor 

  • The installation of lightning rods as a part of a building lightning protection system must be performed by technically qualified. 

 

Installation process

The lightning arresters are generally installed at a fixed and highest elevation (roof) of the building. They are placed on the four corners and one between the two corners. A 16 mm bare grounding cable is connected to the base of the lightning arrester and dropped to the ground floor main panel board grounding terminal. Here is the basic installation process as per UNE guidelines.

  1. The top of the light terminal should be installed at least two meters over the area that it protects (including antennas, refrigerating towers, roofs and tanks, and such). 
  2. The lightning protection devices must have their chassis grounded to the same ground near the building's entrance. 
  3. The primary and secondary lightning protection should be as close to the building's entrance as possible. Wherever feasible, they should be mounted on the grounding plate itself.
  4. Each lightning rod needs to be connected to at least two down conductors. 
  5. The receiving antennas (TV, radio, telephone) should be connected directly or through an SPD or an isolated spark gap to the lightning protection system with a suitable conductor. 
  6. The coaxial cable of the antennas should be protected with a surge protective device. The shield of the coaxial cable should be connected to a grounding plate at the building's entrance. 
  7. The metallic elements that rise above the roof should be connected to the closest down conductor. 
  8. The routing of the down-conductor must be kept as straight as possible, following the shortest path and avoiding sharp bends or upward sections. 
  9. The bend radii must not be less than 20cm. 
  10. Down-conductors will be placed preferably at the external part of the structure (wherever possible) and avoid proximity to electrical or gas conductors. 
  11. For periodical inspections, the grounding system should be placed in a registry cage. 
  12. The registry cage, if present, should be provided with a test joint to disconnect the earth termination system for enabling measurements. In the absence of a registry cage, the down conductors should be used in the same way. 
  13. The resistance value measured using conventional equipment should be the lowest possible (less than 10 Ω). This resistance must be measured on the Earthing termination insulated from any other conductive component. 
  14. All Earthing systems for the same structure need to be interconnected. 

 

The recommendation is to add Quibacsol mineral compound to achieve lower soil resistivity.

 

Primary lightning protection is provided by the electrical operators according to local building codes. The arresters are added as extra protection for the building structure. For indoor equipment protection and safe operation, secondary protection devices installations are within the buildings/ equipment with external antennas.

When you decide to install lightning arrester on building, it's important you choose the best quality.

 

At AXIS, we test our lightning protection products following major international standards such as IEC, BS EN, UNE, and UL & IS. We also provide design solutions including proprietary risk assessment software complying with IEC 62305 -2.

 

Thank you for reading the blog, Axis is a leading manufacturer and supplier of Electrical Components to over 80+ Countries. To get a quote or to talk to our industry expert visit our contact us section. You can also watch our videos by our experts - click here.

Follow us on LinkedIn for regular updates on our Products!

Surge Protection Devices – Complete Overview
Plate Earthing Diagram – Explained |

VISIT US

CONTACT US

© Copyright Reserved by Axis Electrical Components (India) Pvt. Ltd.

× How can we help you?